Water ValveHome>Products
I、Product instruction
This kind of valve is designed and manufactured by our engineer with reference to the same type products domestic and overseas .Body design adopt to full port streamlined .Small Fluid resistance large flow, good sealing effect .As equipped with a catheter on the main valve,using water power ,Can control the water tower or liquid surface of pool automatically,easy maintenance,Flexible and durable,high accuracy liquid level control,Water level without hydraulic interference and tight shutoff no leaking,welcome to purchase
II、Structure
The valve consists of the main valve, pilot valve, needle valve, ball valve, micro filter ,pressure gauge, etc,Due to the pilot valve, needle valve and pressure gauge need to connected the main valve with a catheter , so collectively called catheter control system, as the figure below
1.Body 2.Nut 3.Sealing Ring 4.Disc 5.Stem 6.Diaphragm Press Plate 7.Diaphragm 8.Bolt 9.Bonnet 10.Nut 11.Nut 12.Spring 13.Pressure gauge 14.Ball valve 15.Needle valve 16.Chock plug 17.Pilot valve 18.Ball Valve 19.Pressure gauge 20.Ball valve
DN | Length | Main dimension | |||||||||||
0.6MPa | 1.0MPa | 1.6MPa | 2.5MPa | ||||||||||
mm | L | D | D1 | n-d | D | D1 | n-d | D | D1 | n-d | D | D1 | n-d |
50 | 200 | 140 | 110 | 4-14 | 165 | 125 | 4-18 | 165 | 125 | 4-18 | 165 | 125 | 4-18 |
65 | 220 | 160 | 130 | 4-14 | 185 | 145 | 4-18 | 185 | 145 | 4-18 | 185 | 145 | 8-18 |
80 | 230 | 190 | 150 | 4-18 | 200 | 160 | 8-18 | 200 | 160 | 8-18 | 200 | 160 | 8-18 |
100 | 265 | 210 | 170 | 4-18 | 220 | 180 | 8-18 | 220 | 180 | 8-18 | 235 | 190 | 8-22 |
125 | 295 | 240 | 200 | 8-18 | 250 | 210 | 8-18 | 250 | 210 | 8-18 | 270 | 220 | 8-26 |
150 | 335 | 265 | 225 | 8-18 | 285 | 240 | 8-22 | 285 | 240 | 8-22 | 300 | 250 | 8-26 |
200 | 385 | 320 | 280 | 8-18 | 340 | 295 | 8-22 | 340 | 295 | 12-22 | 360 | 310 | 12-26 |
250 | 465 | 375 | 335 | 12-18 | 395 | 350 | 12-22 | 405 | 355 | 12-26 | 425 | 370 | 12-30 |
300 | 545 | 440 | 395 | 12-22 | 445 | 400 | 12-22 | 460 | 410 | 12-26 | 485 | 430 | 16-30 |
350 | 610 | 490 | 445 | 12-22 | 505 | 460 | 16-22 | 520 | 470 | 16-26 | 555 | 490 | 16-33 |
400 | 650 | 540 | 495 | 16-22 | 565 | 515 | 16-26 | 580 | 525 | 16-30 | 620 | 550 | 16-36 |
450 | 730 | 595 | 550 | 16-22 | 615 | 565 | 20-26 | 640 | 585 | 20-30 | 670 | 600 | 20-36 |
500 | 800 | 645 | 600 | 20-22 | 670 | 620 | 20-26 | 715 | 650 | 20-33 | 730 | 660 | 20-36 |
600 | 920 | 755 | 705 | 20-26 | 780 | 725 | 20-30 | 840 | 770 | 20-36 | 845 | 770 | 20-39 |
III、Working principle
Inlet pressure P1 through catheter and needle valve 15 (see chart) into the control room of the main valve, and establish the downward pressure F3. Outlet pressure P2 can interact through the catheter under 17 of the pilot valve diaphragm and confrontation with the adjustment of the pilot valve spring first. When the downstream pressure exceeds pilot valve spring set value, the pilot valve closed, the control of indoor water excretion is 0, variable pressure reach maximum F3, the main valve plate press the seat valve ,pressure valve closed. When the downstream pressure is less than the pilot valve spring set value, the pilot valve open, control of indoor water will be through the pilot valve17 , ball valve20 exhaust to downstream. Because of the small opening of needle valve (1/4-1/2), and inlet duct diameter is smaller than outlet duct diameter , so the discharge speed is greater than the inlet pressure filling water rate, the F3 is reduced, the inlet pressureP1 act below the main valve plate15 will lift the main valve plate ,so as to open the pressure valve. In stabilization state, excretion is equal to the filling water flow, the main valve mouth opening unchanged, downstream pressure stability.
IV、Main technical date sheet
PN | 1.0MPa | 1.6MPa | 2.5MPa |
Body test pressure | 1.5MPa | 2.4MPa | 3.75MPa |
Sealing test pressure | 1.1MPa | 1.76MPa | 2.75MPa |
Max inlet pressure | 1.0MPa | 1.6MPa | 2.5MPa |
Outlet Pressure adjustable range | 0.09—0.8MPa | 0.10—1.2MPa | 0.15—1.6MPa |
Suitable Temperature | 0℃—80℃ | ||
Suitable Medium | Water |
V、 Installation and adjustment
1.The best installation way of the main valve is horizontal installation, bonnet up, other installation method can reach the use function, thoroughly remove the clutter of pipe before installation . Pay attention to the main valve body outer flow labeled arrows, should follow the direction installation. After installation shall ensure that no pipe stress on the valve body and valve internal parts.
1.Before the main valve need to install a gate valve and a filter, after the main valve also need to install a gate valve, in order to maintenance.
2.The micro filter need to regular cleaning.
3.Must be flushed pipeline thoroughly before water supply.
4.The important water supply management should install by-pass valve.
6.Adjustment method
1)Close the isolation valve upstream, open the downstream isolation pressure relief valve , the downstream pressure drops below 0.1 MPa, close the downstream isolation valve.
2)The pilot valve adjusting screw to the top position;
3)Open upstream isolation valve slowly to fully open;
4)Tighten the pilot valve adjusting screw down slowly, outlet pressure will gradually rise, until the set value will be the adjusting screw locking;
5)If the regulating overdo, must start from the first step to adjust, namely only regulate pressure from low to high.